PT100 to 4-20 mA and 0-10 V, with OLED display and alarm relay

Article number PR515x500

PR515 module in DIN rail enclosure, angled top view: OLED display, push buttons, USB-C port and screw terminals

The PR515x500 measures the temperature with a PT100 sensor in a 2-, 3- or 4-wire connection and passes it on as 4-20 mA and as 0-10 V. Which temperature corresponds to 4 mA and which to 20 mA is set on the OLED display. In addition, a relay contact switches at an adjustable limit, with hysteresis, so the same module can also drive an alarm or a fan. This lets you connect an existing PT100 to a PLC or controller that only has a 4-20 mA or 0-10 V input.

Price on request. Supplied in series, from 10 units per item. Not in stock? Then we build your series. One or a few units only as a trial, for a company with a series in sight.

Specifications

Supply12 and 24 V DC, operating range 11 to 30 V DC
InputPT100, 2-, 3- or 4-wire
Measuring rangeAdjustable, for example −50 to +150 °C
Output4-20 mA (active) and 0-10 V, simultaneously; relay contact (normally open)
IsolationNot galvanically isolated; isolated version as an option
SetupOLED display with UP, DOWN and OK buttons
USBUSB-C for software updates and reading the status
Wi-FiBuilt-in hotspot for software updates
MountingDIN rail, horizontal enclosure
Internally fitted withPR181T23

Setup

  1. Connect the supply, the PT100 and the outputs according to the wiring diagram supplied with the module.
  2. On the display, choose the temperature at 4 mA and at 20 mA (and with it at 0 and 10 V).
  3. Set the relay limit and hysteresis and store with SAVE.