PR100 module in DIN rail holder, front three-quarter view

0-5 V to 0-10 V converter, push-button setup

Article number PR100s05

The PR100s05 scales a 0-5 V DC analogue signal up to 0-10 V DC. The output is calibrated with the push buttons: input at 5 V, press the button for 10 V; input at 0 V, press the button for 0 V. Fine adjustment by hand remains possible afterwards. The output is not galvanically isolated: the output minus is internally connected to the supply minus.

  • Supply 12 and 24 V DC, operating range 11 to 30 V DC
  • Input 0-5 V DC
  • Output 0-10 V DC

Price on request

Lead time on request. Not in stock? We will make it.

Other version: PR181-X092. The PR181-X092 also converts 0-5 V to 0-10 V, with an output galvanically isolated from input and supply. It is set up on a display, and the rise and fall rate of the output is adjustable as well. Supply 9 to 30 V DC, ambient temperature -25 to 55 °C, non-condensing. Do input and output need to be isolated, or would you rather set it up on a display? Then choose the PR181. Otherwise the PR100 is sufficient.

Orders are placed by email with a purchase order. We supply businesses only.

Specifications

Specifications
Supply12 and 24 V DC, operating range 11 to 30 V DC
Input0-5 V DC
Output0-10 V DC
IsolationNot isolated: the output minus (terminal 4) is internally connected to the supply minus (terminal 2)
SetupThree push buttons and a green LED
Ambient temperature0 to 55 °C
DimensionsBoard 43 x 72 mm
MountingDIN rail holder, supplied as standard

Connections

Connections
TerminalFunction
Terminal 1Supply plus, 12 or 24 V DC
Terminal 2Supply minus, also common ground for the analogue signals
Terminal 30-10 V output plus
Terminal 40-10 V output minus, internally connected to terminal 2
Terminal 5Not used
Terminal 60-5 V input plus
Terminal 70-5 V input minus, common ground for the input signal

Datasheet (PDF)PDF, 147 kB

Setup

  1. Set up the module when it is first connected and every time you use a different 0-5 V signal.
  2. Connect the 0-5 V source to terminals 6 (plus) and 7 (minus), and the output to terminals 3 and 4.
  3. Apply 12 or 24 V DC to terminals 1 and 2. The green LED lights continuously.
  4. Hold button 3 for four seconds. The LED flashes green: the module is in programming mode.
  5. Set the input to 5 V, the maximum, for an output of 10 V. Hold button 2 for four seconds. The LED flashes quickly for two seconds.
  6. Set the input to 0 V, the minimum, for an output of 0 V. Hold button 1 for four seconds. The LED flashes quickly for two seconds.
  7. Hold button 3 again for four seconds to save. The LED flashes quickly for two seconds and then lights green continuously. The module is ready for use.
  8. To restore the factory settings: disconnect the supply, hold button 2 and reconnect the supply. If the green LED flashes briefly and quickly, the module has been reset.

Application

  • Scaling a voltage level from 0-5 V to 0-10 V

PR100 series: converters with push-button setup

The converters in the PR100 series are set up with three push buttons and a green LED on the module. Button 3 puts the module in programming mode, button 2 stores the value for the maximum and button 1 the value for the minimum; button 3 saves. The output can then still be fine-tuned by hand. All versions run on 12 and 24 V DC, operating range 11 to 30 V DC, at an ambient temperature of 0 to 55 °C; the board measures 43 x 72 mm and a DIN rail holder is supplied as standard. The output minus is internally connected to the supply minus: the PR100 is not galvanically isolated. To restore the factory settings, disconnect the supply, hold button 2 and reconnect the supply.

Do input and output need to be isolated, or would you rather set it up on a display? Then choose a module from the PR181 series: it is set up on a display, runs on 9 to 30 V DC and has a galvanically isolated output and an adjustable rise and fall rate. Where a PR181 exists for the same conversion, it is listed on the product page under Other version.

More about the PR100 series

Not quite right?

A different input, another range, galvanic isolation or your own logo: we adapt the module.

Question about wiring?

You speak directly with the developer. Call or message Willem on +31 6 45 77 55 93.

PR100s05

Request price and lead time

Enter the quantity. You will receive price and lead time by email. You then order with a purchase order.

The fastest way

Send the article number and quantity via WhatsApp to +31 6 83 66 55 88. Willem replies on working days.

Request

Fields marked * are required.

You can also send photos or drawings via WhatsApp(opens in a new tab).

Request price