PR181 module in DIN rail enclosure, front three-quarter view

0-10 V to 4-20 mA signal conditioner, isolated, with display

Article number PR181-X082

The PR181-X082 converts a 0-10 V voltage into a 4-20 mA current signal. The output is galvanically isolated from the input and the supply to prevent ground loops. Lower and upper limits of input and output are set independently on the display, as is the rise and fall rate of the output. As delivered, 0 V at the input gives 4 mA and 10 V gives 20 mA.

  • Supply 9 to 30 V DC
  • Input 0-10 V on terminal 3, 11 V max.
  • Output 4-20 mA as delivered, 21 mA max.; lower and upper limit adjustable

Price on request

Lead time on request. Not in stock? We will make it.

Other version: PR100s02. The PR100s02 performs the same conversion without a display: it is set up with three push buttons on the module. The output is not isolated (the output minus is connected to the supply minus), the supply is 12 and 24 V DC (operating range 11 to 30 V DC) and the ambient temperature 0 to 55 °C. Do input and output need to be isolated, or would you rather set it up on a display? Then choose the PR181. Otherwise the PR100 is sufficient.

Orders are placed by email with a purchase order. We supply businesses only.

Specifications

Specifications
Supply9 to 30 V DC
Input0-10 V on terminal 3, 11 V max.
Output4-20 mA as delivered, 21 mA max.; lower and upper limit adjustable
IsolationOutput galvanically isolated from input and supply
SetupDisplay with UP, OK and DOWN buttons
Rise and fall rateAdjustable on the display
Ambient temperature-25 to 55 °C, non-condensing
Dimensions45 x 83 mm with DIN rail enclosure, 42.6 x 72 mm without
Factory setting0 V input = 4 mA, 10 V = 20 mA

Connections

Connections
TerminalFunction
Terminal 1Supply plus
Terminal 2Supply minus
Terminal 30-10 V input (plus)
Terminal 4Not used
Terminal 5Not used
Terminal 6Isolated output common
Terminal 7Isolated 4-20 mA output (plus)
Terminal 8Not used

Datasheet (PDF)PDF, 142 kB

Setup

  1. Connect the module according to the terminal table and switch on the supply.
  2. Set the input to its lowest level, for example 0 V. In the menu, select IN1 – Set minimum, press OK, select YES and press OK again.
  3. Set the input to its highest level, for example 10 V. Select IN1 – Set maximum, press OK, select YES and press OK again.
  4. Set the lower limit of the output with OUT1 minimum adj: change the value with UP and DOWN and confirm with OK.
  5. Set the upper limit of the output in the same way with OUT1 maximum adj.
  6. If required, set the rise and fall rate of the output with IN1 Ramp-Up and IN1 Ramp-Down.
  7. Fine adjustment: IN1 minimum adj and IN1 maximum adj fine-tune the input limits. Setting OUT1 invert to 1 reverses the output: the lowest input level then gives the highest output level.
  8. Go to the SAVE menu to store the new settings.

Application

  • Connecting a 0-10 V signal to a 4-20 mA input, with galvanic isolation to prevent ground loops
  • Driving motors, pumps, valves and hydraulics smoothly with the adjustable rise and fall rate

PR181 series: signal conditioners with display

The modules in the PR181 series are set up on the display on the module, using the UP, DOWN and OK buttons. On most versions the lower and upper limits of input and output are set independently, as is the rise and fall rate of the output; the settings of each module are listed on the product page under Setup. With an adjustable rise and fall rate, motors, pumps, valves and hydraulics can be driven smoothly. On versions with an analogue output, that output is galvanically isolated from input and supply to prevent ground loops. New settings are stored through the SAVE menu. The standard DIN rail enclosure measures 45 x 83 mm (board 42.6 x 72 mm); versions with more terminals are wider. Most modules run on 9 to 30 V DC at -25 to 55 °C, non-condensing.

For some conversions there is also a version without display and without galvanic isolation in the PR100 series: it is set up with push buttons and runs on 12 and 24 V DC (operating range 11 to 30 V DC). Where one exists, it is listed on the product page under Other version.

More about the PR181 series

Not quite right?

A different input, another range, galvanic isolation or your own logo: we adapt the module.

Question about wiring?

You speak directly with the developer. Call or message Willem on +31 6 45 77 55 93.

PR181-X082

Request price and lead time

Enter the quantity. You will receive price and lead time by email. You then order with a purchase order.

The fastest way

Send the article number and quantity via WhatsApp to +31 6 83 66 55 88. Willem replies on working days.

Request

Fields marked * are required.

You can also send photos or drawings via WhatsApp(opens in a new tab).

Request price