Not quite right?
A different input, another range, galvanic isolation or your own logo: we adapt the module.
Article number PR181-X080
The PR181-X080 converts a voltage of -10 to +10 V into 0-10 V. Input and output are galvanically isolated from each other and from the supply to prevent ground loops. If the input signal is lost, for example due to a broken wire, the output goes to 5 V, so that no unexpected output level occurs. As delivered, -10 V at the input gives 0 V, 0 V gives 5 V and +10 V gives 10 V.
Price on request
Lead time on request. Not in stock? We will make it.
Orders are placed by email with a purchase order. We supply businesses only.
| Supply | 9 to 30 V DC |
|---|---|
| Input | ±10 V on terminals 11 (signal) and 12 (common), -11 to +11 V max. |
| Output | 0-10 V; lower and upper limit adjustable |
| Isolation | Input and output galvanically isolated from each other and from the supply |
| Setup | Display with UP, OK and DOWN buttons |
| On signal loss | Output goes to 5 V if the input signal is lost, for example due to a broken wire |
| Rise and fall rate | Adjustable on the display |
| Ambient temperature | -25 to 55 °C, non-condensing |
| Dimensions | 68 x 83 mm with DIN rail enclosure, 65 x 72 mm without |
| Factory setting | -10 V input = 0 V, 0 V = 5 V, +10 V = 10 V |
| Terminal | Function |
|---|---|
| Terminal 1 | Supply plus |
| Terminal 2 | Supply minus |
| Terminal 3 | Minus, internally connected to terminal 2 |
| Terminal 4 | Not used |
| Terminal 5 | Not used |
| Terminal 6 | Not used |
| Terminal 7 | Isolated output common |
| Terminal 8 | Isolated 0-10 V output (plus) |
| Terminal 9 | Not used |
| Terminal 10 | Not used |
| Terminal 11 | Isolated ±10 V input (signal) |
| Terminal 12 | Isolated input common |
The modules in the PR181 series are set up on the display on the module, using the UP, DOWN and OK buttons. On most versions the lower and upper limits of input and output are set independently, as is the rise and fall rate of the output; the settings of each module are listed on the product page under Setup. With an adjustable rise and fall rate, motors, pumps, valves and hydraulics can be driven smoothly. On versions with an analogue output, that output is galvanically isolated from input and supply to prevent ground loops. New settings are stored through the SAVE menu. The standard DIN rail enclosure measures 45 x 83 mm (board 42.6 x 72 mm); versions with more terminals are wider. Most modules run on 9 to 30 V DC at -25 to 55 °C, non-condensing.
For some conversions there is also a version without display and without galvanic isolation in the PR100 series: it is set up with push buttons and runs on 12 and 24 V DC (operating range 11 to 30 V DC). Where one exists, it is listed on the product page under Other version.
A different input, another range, galvanic isolation or your own logo: we adapt the module.
You speak directly with the developer. Call or message Willem on +31 6 45 77 55 93.
PR181-X080
Enter the quantity. You will receive price and lead time by email. You then order with a purchase order.
Send the article number and quantity via WhatsApp to +31 6 83 66 55 88. Willem replies on working days.