PR157s08 in DIN rail enclosure, front three-quarter view: relays, terminals for inputs and relay outputs

8 isolated inputs and 8 relay outputs via CAN bus

Article number PR157s08

The PR157s08 combines eight digital inputs, a potentiometer input and eight relay outputs on one DIN rail module. The inputs accept 24 V signals, each have their own plus and minus terminal and are optically isolated from the outputs, the potentiometer input and the supply. The relay outputs are galvanically isolated from the supply and the inputs and switch up to 24 V DC and 5 A.

  • Supply 24 V DC
  • Input 8 digital inputs of 24 V DC, 6.7 mA per input at 24 V; potentiometer input for 1 kΩ to 100 kΩ
  • Output 8 relays, each with NO, COM and NC terminal; 24 V DC, 5 A DC max.

Price on request

Lead time on request. Not in stock? We will make it.

Orders are placed by email with a purchase order. We supply businesses only.

Specifications

Specifications
Supply24 V DC
Input8 digital inputs of 24 V DC, 6.7 mA per input at 24 V; potentiometer input for 1 kΩ to 100 kΩ
Output8 relays, each with NO, COM and NC terminal; 24 V DC, 5 A DC max.
IsolationDigital inputs optically isolated from outputs, potentiometer input and supply; relay outputs galvanically isolated from supply and inputs
CommunicationCAN bus; 120 Ω termination enabled with jumper JP1
IndicationStatus LED per input and output; PWR and ACT LEDs
Dimensions170 x 83 mm with DIN rail enclosure, 166.8 x 72 mm without
MountingDIN rail

Connections

Connections
TerminalFunction
Terminal +24VSupply plus
Terminal -24VSupply minus (0 V)
Terminal CAN SCRCAN bus cable shield
Terminal CANLCAN bus low
Terminal CANHCAN bus high
Terminal IN1+ – IN8+Plus of input 1 to 8 (+24 V of the input signal)
Terminal IN1- – IN8-Minus of input 1 to 8
Terminal SCRPotentiometer minus
Terminal SignalPotentiometer signal (wiper)
Terminal PPPotentiometer plus
Terminal OUT1 NC – OUT8 NCNormally closed contact (NC) of output 1 to 8
Terminal OUT1 COM – OUT8 COMCommon contact (COM) of output 1 to 8
Terminal OUT1 NO – OUT8 NONormally open contact (NO) of output 1 to 8

Datasheet (PDF)PDF, 164 kB

Setup

  1. Connect the module according to the terminal table.
  2. If the module sits at one end of the CAN bus network, fit jumper JP1: it terminates the bus with 120 Ω. Both ends of the network must be terminated like this.

PR157 series: I/O and communication modules for DIN rail

The PR157 series consists of DIN rail modules. The CAN bus versions read optically isolated 24 V inputs and a potentiometer, or switch relay outputs (24 V DC, 5 A) with separate NO, COM and NC terminals per output; status LEDs show the state of each input or output. Terminate both ends of the CAN bus network with 120 Ω: fit jumper JP1 on the module at the end of the network. More inputs or outputs, or control via RS485 and Modbus instead of CAN bus, are available on request for these versions.

More about the PR157 series

Not quite right?

A different input, another range, galvanic isolation or your own logo: we adapt the module.

Question about wiring?

You speak directly with the developer. Call or message Willem on +31 6 45 77 55 93.

PR157s08

Request price and lead time

Enter the quantity. You will receive price and lead time by email. You then order with a purchase order.

The fastest way

Send the article number and quantity via WhatsApp to +31 6 83 66 55 88. Willem replies on working days.

Request

Fields marked * are required.

You can also send photos or drawings via WhatsApp(opens in a new tab).

Request price