PR157s12 in DIN rail enclosure, front three-quarter view: eight relays and the output terminals

8 relay outputs via CAN bus

Article number PR157s12

The PR157s12 has eight relay outputs that are switched via the CAN bus. Each output has its own normally open, common and normally closed contact, so you choose per output whether a circuit is closed or opened. The relay outputs are galvanically isolated from the supply and switch up to 24 V DC and 5 A.

  • Supply 24 V DC
  • Output 8 relays, each with NO, COM and NC terminal; 24 V DC, 5 A DC max.
  • Isolation relay outputs galvanically isolated from the supply

Price on request

Lead time on request. Not in stock? We will make it.

Orders are placed by email with a purchase order. We supply businesses only.

Specifications

Specifications
Supply24 V DC
Output8 relays, each with NO, COM and NC terminal; 24 V DC, 5 A DC max.
IsolationRelay outputs galvanically isolated from the supply
CommunicationCAN bus; 120 Ω termination enabled with jumper JP1
IndicationStatus LED per output; PWR and ACT LEDs
Dimensions102 x 83 mm with DIN rail enclosure, 98.75 x 72 mm without
MountingDIN rail

Connections

Connections
TerminalFunction
Terminal +24VSupply plus
Terminal -24VSupply minus (0 V)
Terminal OUT1 NO – OUT8 NONormally open contact (NO) of output 1 to 8
Terminal OUT1 COM – OUT8 COMCommon contact (COM) of output 1 to 8
Terminal OUT1 NC – OUT8 NCNormally closed contact (NC) of output 1 to 8
Terminal CAN SCRCAN bus cable shield
Terminal CANLCAN bus low
Terminal CANHCAN bus high

Datasheet (PDF)PDF, 157 kB

Setup

  1. Connect the module according to the terminal table.
  2. If the module sits at one end of the CAN bus network, fit jumper JP1: it terminates the bus with 120 Ω. Both ends of the network must be terminated like this.

PR157 series: I/O and communication modules for DIN rail

The PR157 series consists of DIN rail modules. The CAN bus versions read optically isolated 24 V inputs and a potentiometer, or switch relay outputs (24 V DC, 5 A) with separate NO, COM and NC terminals per output; status LEDs show the state of each input or output. Terminate both ends of the CAN bus network with 120 Ω: fit jumper JP1 on the module at the end of the network. More inputs or outputs, or control via RS485 and Modbus instead of CAN bus, are available on request for these versions.

More about the PR157 series

Not quite right?

A different input, another range, galvanic isolation or your own logo: we adapt the module.

Question about wiring?

You speak directly with the developer. Call or message Willem on +31 6 45 77 55 93.

PR157s12

Request price and lead time

Enter the quantity. You will receive price and lead time by email. You then order with a purchase order.

The fastest way

Send the article number and quantity via WhatsApp to +31 6 83 66 55 88. Willem replies on working days.

Request