Article number PR181-X087
The PR181-X087 converts the pulses of two contacts, one for up (UP) and one for down (DOWN), into two 4-20 mA signals. Input, outputs and supply are galvanically isolated from each other, and the two outputs from one another as well. When the limit input is active, the outputs cannot rise above the set limit; if an output is higher at that moment, it jumps straight to the limit. The pulse inputs accept high-side or low-side switched contacts; LED 1 (up) and LED 2 (down) light up on a pulse.
Price on request
Lead time on request. Not in stock? We will make it.
Orders are placed by email with a purchase order. We supply businesses only.
| Supply | 9 to 30 V DC |
|---|---|
| Input | Two pulse inputs, UP and DOWN, 20 to 50 V DC; high-side or low-side switched contacts |
| Output | Two 4-20 mA outputs as delivered, 21 mA max.; lower and upper limit adjustable per output |
| Isolation | Input, outputs and supply galvanically isolated from each other; the two outputs also from one another |
| Setup | Display with UP, OK and DOWN buttons |
| Minimum pulse width | 100 ms |
| Limit enable input | On terminal 10; active above 15 V, 34 V absolute maximum |
| Output refresh rate | 10 Hz |
| Rise and fall rate | Adjustable on the display |
| Ambient temperature | -25 to 55 °C, non-condensing |
| Dimensions | 114 x 83 mm with DIN rail enclosure, 110 x 72 mm without |
| Factory setting | Both outputs 4-20 mA; output limit 100 % |
| Terminal | Function |
|---|---|
| Terminal 1 | Supply plus |
| Terminal 2 | Supply minus |
| Terminal 3 | Minus, internally connected to terminal 2 |
| Terminal 4 | Pulse inputs common (Input common) |
| Terminal 5 | Pulse input UP |
| Terminal 6 | Pulse input DOWN |
| Terminal 7 | Isolated common of output 1 |
| Terminal 8 | Isolated output 1, 4-20 mA (plus) |
| Terminal 9 | Not used |
| Terminal 10 | Limit input (Output limit enable) |
| Terminal 11 | Not used |
| Terminal 12 | Not used |
| Terminal 13 | Not used |
| Terminal 14 | Not used |
| Terminal 15 | Not used |
| Terminal 16 | Not used |
| Terminal 17 | Not used |
| Terminal 18 | Not used |
| Terminal 19 | Isolated common of output 2 |
| Terminal 20 | Isolated output 2, 4-20 mA (plus) |
| Terminal 21 | Not used |
The modules in the PR181 series are set up on the display on the module, using the UP, DOWN and OK buttons. On most versions the lower and upper limits of input and output are set independently, as is the rise and fall rate of the output; the settings of each module are listed on the product page under Setup. With an adjustable rise and fall rate, motors, pumps, valves and hydraulics can be driven smoothly. On versions with an analogue output, that output is galvanically isolated from input and supply to prevent ground loops. New settings are stored through the SAVE menu. The standard DIN rail enclosure measures 45 x 83 mm (board 42.6 x 72 mm); versions with more terminals are wider. Most modules run on 9 to 30 V DC at -25 to 55 °C, non-condensing.
For some conversions there is also a version without display and without galvanic isolation in the PR100 series: it is set up with push buttons and runs on 12 and 24 V DC (operating range 11 to 30 V DC). Where one exists, it is listed on the product page under Other version.
A different input, another range, galvanic isolation or your own logo: we adapt the module.
You speak directly with the developer. Call or message Willem on +31 6 45 77 55 93.
PR181-X087
Enter the quantity. You will receive price and lead time by email. You then order with a purchase order.
Send the article number and quantity via WhatsApp to +31 6 83 66 55 88. Willem replies on working days.
WhatsApp Willem(opens in a new tab)